Field manual · Air Conditioner

Lennox XC21 air conditioner and XP21 heat pump (Dave Lennox Signature, iComfort-enabled): quick sheet

Covers: Lennox XC21 (air conditioner, service literature Corp. 1007-L2) and XP21 (heat pump, Corp. 1031-L7), 2, 3, 4 and 5 ton, R-410A, expansion valve indoor coils only. Both use an A175 main control (outdoor control part number 101798-xx) that works in communicating (iComfort) or conventional 24 V mode, plus a separate fan motor control. The XP21 literature describes a two-stage scroll compressor; the 2018 XC21 literature describes the compressor as one-stage while the same control section covers two-stage units, so confirm staging on the nameplate. For ML14XC1/EL16XC1 single-stage units see the separate sheet.

Single sourceBrands: Lennox4 components

In conventional mode the A175 shows diagnostics on two LED pairs: DS11 (green) and DS14 (red) for system status, fault and lockout codes, and DS15 (yellow) and DS13 (red) for compressor fault and lockout codes. Newer controls also have a seven-segment display that shows unit type, capacity and fan profile on power-up. With an iComfort thermostat the same events appear as numbered alert codes (400-series).

Safety first

  • Pressure, charge and compressor replacement work are for an EPA 608 certified technician.
  • Single-pole contactors leave one leg live: lock out the disconnect.

How it works

Only the latest active fault or lockout shows; with none active, the status LEDs show normal operation.

Unit capacity and fan profile must be configured on a new or replacement control (via the FIELD TEST pins E33 or the push button / seven-segment display, depending on revision). Three bars on the display during power-up mean the control was not configured.

XP21 defrost: termination temperature is set by a jumper (factory 50 F); with no jumper the default is 90 F; the coil sensor RT21 measures it.

Compressor fault LEDs are monitoring only; they do not provide safety protection.

Components & tests

Unlock all 4 components, specs, service mode and teardown

Full library + AI assistant + the OnCall Tech app for iPhone & Android. $34.90, one time.

Get lifetime access

Official manufacturer documentation

Always confirm values against the tech sheet for the exact model.

OnCall Tech is a reference tool for trained technicians and can make mistakes. Always disconnect power and confirm with the manufacturer's documentation before you work. © 2026 OnCall Tech. Original content; not a reproduction of any manufacturer document.Generic part photos (not of this brand): Air-source heat pump outdoor unit beside a house in the snow by PeterEastern, CC BY-SA 4.0

Diagnostic guides for this appliance

Other air conditioners manuals

Manual · Air Conditioner

Carrier Infinity Greenspeed 24VNA6 air conditioner and 25VNA4 heat pump (variable speed): quick sheet

Carrier Infinity Greenspeed Intelligence variable-speed outdoor units: 24VNA6 air conditioner (up to 26 SEER) and 25VNA4 heat pump (up to 24 SEER, up to 13 HSPF), 2-5 ton. Nomenclature from the service manual: 24 = AC, 25 = HP; V = variable speed; N = Infinity series; A = Puron (R-410A); 6 / 4 = SEER tier; two digits = nominal capacity (e.g. 36 = 36,000 BTU/h); voltage digit 3 = 208/230-1; compressor ID 4 = variable-speed scroll, 5 = variable-speed rotary. Serial format: week + year + plant letter + sequence (e.g. 0118E00001). Other 24VNA families (24VNA0, 24VNA9) use different software and code lists.

5 components4 common failuresCarrier
Manual · Air Conditioner

Trane XV20i / XV18 variable-speed outdoor units (4TTV0 AC, 4TWV0 heat pump, ComfortLink II): quick sheet

Trane variable-speed TruComfort / ComfortLink II communicating outdoor units: 4TTV0 air conditioners (XV20i family, e.g. 4TTV0024A1000C, 4TTV0036, 4TTV0048, 4TTV0060, 4TTV0061) and 4TWV0 heat pumps (Service Facts 4T-V0-SF). They use an Integrated Variable Speed Control (IVSC) board and a Communicating Display Assembly (CDA) in the outdoor unit. Distributor listings note several 4TTV0 revisions; confirm the full model on the nameplate before ordering parts. Single-stage XR14/XR16 units are on a separate sheet.

4 components3 common failuresTrane
Manual · Air Conditioner

Goodman / Amana ComfortNet two-stage condensers and heat pumps (GSXC, DSXC, ASXC, GSZC, ASZC 16-18 SEER): quick sheet

Goodman (G), Goodman Deluxe (D) and Amana (A) communicating-ready two-stage split units: SXC = air conditioner, SZC = heat pump; 16 or 18 = SEER class; then capacity (024-060) and voltage digit (1 = 208/230 V single phase), e.g. GSXC180481, DSXC160361, ASZC180601. Revisions moved through Copeland UltraTech 2-stage scroll compressors (later UltraTech 3) and 7 mm coils. They work with a ComfortNet communicating thermostat over a 4-wire connection or with conventional 2-stage 24 V thermostats. Single-stage GSX/GSZ units are on a separate sheet.

4 components4 common failuresGoodman, Amana, Daikin
Lennox XC21 air conditioner and XP21 heat pump (Dave Lennox Signature, iComfort-enabled): quick sheet · OnCall Tech