Friedrich Vert-I-Pak A-Series VHA vertical packaged heat pumps (closet units, R-410A): quick sheet with error codes
Covers: Friedrich Vert-I-Pak (VPAK) A-Series vertical packaged terminal heat pumps installed in a closet against an exterior wall with a VPAWP wall plenum and louver: VHA09K, VHA09R, VHA12K, VHA12R, VHA18K, VHA18R, VHA24K, VHA24R. VHA = Vert-I-Pak heat pump A-series; 09-24 = nominal cooling in thousands of BTU/h; K = 208-230 V, R = 265 V. Heater sizes 2.5 / 3.4 / 5.0 kW (plus 7.5 kW on 18 and 7.5 / 10.0 kW on 24). Optional fresh-air module (single F or dual D option). Search terms: VHA09K, VHA12K, VHA18K, VHA24K, Friedrich VPAK error code, VPAWP wall plenum.
A vertical PTAC: chassis and coils in a closet, outdoor air through a wall plenum, ducted supply, and a 24 V wall thermostat. The control logs numbered error codes with a history count and shows a wrench icon when maintenance is due. Many codes are logged while the unit keeps running on a default value, so the code tells you where to look even when the unit still works.
Safety first
- Lock out power before pulling the chassis; 265 V units are hard-wired.
- R-410A refrigerant work is blocked: EPA 608-certified technician.
How it works
Control display: four digits; the left two show the error code (1-24) with On/Off icons for the current state, the right two show the history count (up to 99).
Sensor faults fall back to defaults: indoor sensor 75 °F (cool) / 68 °F (heat); indoor coil 40 °F; outdoor coil 20 °F (and electric heat in heating if available).
Heat pump defrost: active defrost for at least 6 minutes when heat-pump run time exceeds 60 minutes and the outdoor coil is 26 °F or less (code 23 logs it).
Room freeze protection (code 10) runs high fan and electric heat until the room reaches 46 °F; the display shows FRZ.
Components & tests
Unlock all 5 components, specs, service mode and teardown
Full library + AI assistant + the OnCall Tech app for iPhone & Android. $34.90, one time.
Get lifetime accessOfficial manufacturer documentation
Always confirm values against the tech sheet for the exact model.
- Friedrich ZoneAire Select PTAC installation and operation manual (PZE / PZH)
- Friedrich ZoneAire Select PTAC submittal (specs, cord kits, accessories)
- Friedrich Uni-Fit R-32 installation and operation manual (UCT / UET)
- Friedrich Uni-Fit submittal (specs, sleeve sizes, plug types)
- Friedrich Chill Premier service and parts manual (CCF / CCW / CEW, R-32)
- Friedrich Kuhl R-32 installation and operation manual (diagnostic codes)
- Friedrich Kuhl Q chassis service and parts manual
- Friedrich WallMaster installation and operation manual (WCT / WET / WHT, WSE sleeve)
- Friedrich FreshAire PTAC (PV series, R-32) installation and operation manual
- Friedrich Vert-I-Pak (VPAK) installation and operation manual 95991017_02
- Friedrich PTAC (PDE / PDH, R-32, SG chassis) service manual 94142000
- Friedrich ZoneAire Compact single-hose portable with heat (P08SA / P10SA / P12SA) manual
OnCall Tech is a reference tool for trained technicians and can make mistakes. Always disconnect power and confirm with the manufacturer's documentation before you work. © 2026 OnCall Tech. Original content; not a reproduction of any manufacturer document.Generic part photos (not of this brand): Packaged terminal air conditioner (PTAC) under a window with its control door open, showing the set temperature and mode buttons by Central Avenue, CC BY 4.0