Field manual · Air Conditioner

Friedrich PDE / PDH digital PTACs, R-32 SG chassis (2022+): quick sheet with F/E/A/H codes

Covers: Friedrich standard-chassis digital PTACs on R-32 covered by service manual 94142000: PDE (cool with electric heat) and PDH (heat pump) in 7,000-15,000 BTU/h sizes, e.g. PDE07K3SGR3, PDE07R3SGR3, PDE09K3SGR3, PDE09R3SGR3 and the guide example PDH09K3SGR3 (12,000-15,000 BTU/h electric-heat and heat-pump sizes are also in the manual). Model guide: P = PTAC, D = digital, E or H = cool only with electric heat / heat pump, two digits = approximate cooling BTU/h, voltage K = 230/208 V or R = 265 V, heater digit 2 = 2.5 kW, 3 = 3.5 kW, 5 = 5 kW, then SG series and R3 for R-32. Serial guide: first two digits = year (22 = 2022 ... 25 = 2025), next two = month, then a manufacturing location letter and a 5-digit sequence starting at 00001 each month (e.g. 1712M00001). Older R-410A PDE/PDH units may use a different code set. Search terms: PDH09K3SGR3, PDE09K3SGR3, Friedrich PTAC F0, Friedrich PTAC A2, Friedrich PTAC U5.

Single sourceBrands: Friedrich5 components

This PTAC has a logic PCB, a separate power PCB with current-sensing (CT) loops, a display PCB and a status LED on the main board. Major faults shut the unit down and show a code on the two-digit display; minor self-correcting conditions are only flashed on the status LED (visible with the front removed). Codes cover sensors (F1-F4, FJ), protections (FP, F0, H3, E5), heater circuit faults (A0, A2, A4, C7) and current imbalance (U5).

Safety first

  • Unplug before opening; capacitors and PCBs hold charge.
  • R-32 is mildly flammable; refrigerant work is blocked and goes to an EPA 608-certified technician.

How it works

Sensors: indoor ambient 15 kOhm at 77 °F; indoor coil, outdoor ambient, condenser coil and discharge sensors 20 kOhm at 77 °F (Friedrich table).

Cooling freeze protection (status LED 5 flashes): compressor and outdoor fan stop, indoor fan runs; resumes when the indoor coil reads 40 °F or more for 2 minutes.

Heat pump frost prevention (7 flashes): compressor and outdoor fan stop; electric heat after 15 s if heat is called; compressor available again after the sensor reads 40 °F or more for 10 minutes.

Heating high-temperature protection of the evaporator (8 flashes): compressor and outdoor fan stop, electric heat enabled after 15 s; returns when the coil reads 126 °F or less for 2 minutes.

FP low-temperature protection: room below 40 °F continuously; unit runs electric heat only until the room reaches 50 °F.

Components & tests

Unlock all 5 components, specs, service mode and teardown

Full library + AI assistant + the OnCall Tech app for iPhone & Android. $34.90, one time.

Get lifetime access

Official manufacturer documentation

Always confirm values against the tech sheet for the exact model.

OnCall Tech is a reference tool for trained technicians and can make mistakes. Always disconnect power and confirm with the manufacturer's documentation before you work. © 2026 OnCall Tech. Original content; not a reproduction of any manufacturer document.Generic part photos (not of this brand): Packaged terminal air conditioner (PTAC) under a window with its control door open, showing the set temperature and mode buttons by Central Avenue, CC BY 4.0

Diagnostic guides for this appliance

Other air conditioners manuals

Manual · Air Conditioner

Carrier Infinity Greenspeed 24VNA6 air conditioner and 25VNA4 heat pump (variable speed): quick sheet

Carrier Infinity Greenspeed Intelligence variable-speed outdoor units: 24VNA6 air conditioner (up to 26 SEER) and 25VNA4 heat pump (up to 24 SEER, up to 13 HSPF), 2-5 ton. Nomenclature from the service manual: 24 = AC, 25 = HP; V = variable speed; N = Infinity series; A = Puron (R-410A); 6 / 4 = SEER tier; two digits = nominal capacity (e.g. 36 = 36,000 BTU/h); voltage digit 3 = 208/230-1; compressor ID 4 = variable-speed scroll, 5 = variable-speed rotary. Serial format: week + year + plant letter + sequence (e.g. 0118E00001). Other 24VNA families (24VNA0, 24VNA9) use different software and code lists.

5 components4 common failuresCarrier
Manual · Air Conditioner

Trane XV20i / XV18 variable-speed outdoor units (4TTV0 AC, 4TWV0 heat pump, ComfortLink II): quick sheet

Trane variable-speed TruComfort / ComfortLink II communicating outdoor units: 4TTV0 air conditioners (XV20i family, e.g. 4TTV0024A1000C, 4TTV0036, 4TTV0048, 4TTV0060, 4TTV0061) and 4TWV0 heat pumps (Service Facts 4T-V0-SF). They use an Integrated Variable Speed Control (IVSC) board and a Communicating Display Assembly (CDA) in the outdoor unit. Distributor listings note several 4TTV0 revisions; confirm the full model on the nameplate before ordering parts. Single-stage XR14/XR16 units are on a separate sheet.

4 components3 common failuresTrane
Manual · Air Conditioner

Lennox XC21 air conditioner and XP21 heat pump (Dave Lennox Signature, iComfort-enabled): quick sheet

Lennox XC21 (air conditioner, service literature Corp. 1007-L2) and XP21 (heat pump, Corp. 1031-L7), 2, 3, 4 and 5 ton, R-410A, expansion valve indoor coils only. Both use an A175 main control (outdoor control part number 101798-xx) that works in communicating (iComfort) or conventional 24 V mode, plus a separate fan motor control. The XP21 literature describes a two-stage scroll compressor; the 2018 XC21 literature describes the compressor as one-stage while the same control section covers two-stage units, so confirm staging on the nameplate. For ML14XC1/EL16XC1 single-stage units see the separate sheet.

4 components3 common failuresLennox
Friedrich PDE / PDH digital PTACs, R-32 SG chassis (2022+): quick sheet with F/E/A/H codes · OnCall Tech