5 components coveredField manual · Air Conditioner
Amana PTC / PTH DigiSmart PTACs and PTHPs (G design series, R-410A): quick sheet
Covers: Amana-brand packaged terminal units built by Goodman (Daikin group) with the DigiSmart electronic control: PTC (cooling with electric heat), PTH (heat pump with electric backup) and DRY (dehumidifying cooler). Model pattern from Amana's spec sheet SS-DPTAC: PT + C or H + capacity (07, 09, 12, 15, 17 = 7,000-17,000 BTU/h) + voltage digit (2 = 115 V, 3 = 230/208 V, 4 = 265 V, 5 = 240/220 V 50 Hz) + design series (G = R-410A) + two-digit heater size (00 none, 15 = 1.5 kW, 25 = 2.5 kW, 35 = 3.5 kW at 230/208 V or 3.7 kW at 265 V, 50 = 5.0 kW) + feature letters (A standard, C seacoast corrosion protection, D power door, F fuse holder, H hydronic-capable, P condensate pump on PTH, Q quiet chassis, R RF antenna, V power vent, W hard-wired) + placeholders X, e.g. PTC073G35AXXX, PTH123G35AXXX, PTC094G50AXXX. Search terms: PTC093G35AXXX, PTH123G35AXXX, PTH153G50AXXX, Amana DigiSmart diagnostic codes. Older B-series and earlier Amana PTACs are not covered.
DigiSmart PTACs slide into a standard 42-inch PTAC sleeve. The board can be run from the chassis keypad, a wired 24 V thermostat or a wireless (RF) thermostat, and it shows two-character diagnostic codes on the LED display. On 230/208 V the heater size is set by the cord, so the cord, receptacle and breaker must agree; 265 V units need an Amana subbase or hard-wire kit.
Safety first
- Unplug or lock out before opening the control box.
- 265 V units are hard-wired or on a subbase: verify 0 V before touching terminals.
- Refrigerant work is blocked: refer to an EPA 608-certified technician.
How it works
230/208 V and 115 V units (all models under 250 V) use an LCDI cord. Amana's table pairs the cord with heater size: 2.5 kW on a 6-15P (15 A), 3.5 kW on a 6-20P (20 A), 5.0 kW on a 6-30P (30 A).
265 V units must use an Amana subbase (PTSB4**E) or hard-wire kit (PTPWHWK4); overcurrent protection is by factory-installed cartridge time-delay fuses.
PTH heat pumps switch automatically to electric heat at about 24 °F outdoor ambient (Amana spec sheet).
Voltage window per Amana: 230/208 V models 197-253 V; 265 V models 239-292 V; 115 V models 109-127 V.
Components & tests
Unlock all 5 components, specs, service mode and teardown
Full library + AI assistant + the OnCall Tech app for iPhone & Android. $34.90, one time.
Get lifetime accessOfficial manufacturer documentation
Always confirm values against the tech sheet for the exact model.
OnCall Tech is a reference tool for trained technicians and can make mistakes. Always disconnect power and confirm with the manufacturer's documentation before you work. © 2026 OnCall Tech. Original content; not a reproduction of any manufacturer document.Generic part photos (not of this brand): Packaged terminal air conditioner (PTAC) under a window with its control door open, showing the set temperature and mode buttons by Central Avenue, CC BY 4.0