Ghost voltage and triac leakage: why the meter shows voltage on a wire or board output that is really off
A high-impedance digital meter barely loads the circuit, so it can show voltage coupled capacitively from nearby live wires (ghost voltage) or the small leakage current through a solid-state switch such as a triac that is off. With the real load connected, or with a low-impedance (LoZ) meter function, those readings collapse toward zero; a real supply does not. Knowing this keeps you from condemning a good board or trusting a reading that is not there.
Before you start
- A floating reading near line voltage can still shock you; treat the conductor as live until proven otherwise
- LoZ functions load the circuit: do not use them on sensitive electronic signal circuits, and expect a LoZ test from hot to ground to trip a GFCI
- Measure with power on only with insulated probes and one hand where possible